Leave all documentation received with appliance with owner for future reference. WARNING - Input from 100,000 to 199,000 Btu/hr - NOTICE If the information in this manual is not followed exactly, a fire or explosion may result causing pro p e rty damage, personal injury or d e a t h . FOR YOUR SAFETY • Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. • WHAT TO DO IF YOU SMELL GAS -Do not try to light any appliance -Do not touch an
-Connect a voltmeter across the end terminals of the male half of the Room Thermostat Snap-set. -Close each thermostat, zone valve and relay in the external circuit one zone at a time and check the voltage reading across the plug. -There should NEVER be voltage measured at the plug. -If voltage is measured at the plug under any condition, check and correct the external wiring. NOTICE In systems using 3-wire zone valves backfeed of voltage to the unit is a common problem. Use an isolation relay t
• Outer tank has a factory installed 30 psig relief valve rated at 535,000 Btu/hr • Electrical rating:120 V, 60 Hz, less than 12 amperes • pH & chloride limits for the ELITE are: -Chloride, less than 80 mg/l. -pH, 6.0 - 8.0. NOTICE Any water conditioning system must be installed and maintained in accordance with manufacturer’s specifications. • 180. Maximum operating temperature primary side. • 120. Maximum outlet/mixed temperature - domestic side. CODE RESTRICTIONS Single wall heat exchanger in
WARNING Failure to apply pipe dope as detailed above can result in severe personal injury, death or substantial property damage. WARNING Use a two-wrench method of tightening gas piping near the unit and its gas valve. Use one wrench to prevent the gas valve line connection from turning and the second to tighten adjacent piping. Failure to support the gas valve connection piping could damage the valve and the gas line components. Fig. 15: Recommended Gas Supply Piping 28 Fuel Piping Pipe Sizing
Failure to install a heat exchanger could lead to premature failure of the outer tank and void any warranty claim. WARNING Radiant heating system piping should include a means of regulating the boiler return water. The return water temperature to the unit should be maintained at 130.F or higher. Failure to prevent low return water temperature to the unit could cause premature failure of the unit and it’s burner system resulting in severe personal injury, death or substantial property damage. Siz
3. Remove the hose from the primary drain valve when draining is complete. 4. Remove the plugs, nipple, shut-off valve and any other piping unless they will remain for use in the system piping. 10 Domestic Piping SECTION IV - Domestic Piping General Piping Requirements • All plumbing must meet or exceed all local, state and national plumbing codes. • Use pipe dope or tape suitable for potable water. • Use isolation valves to isolate system components. • Install unions for easy removal of the ELI