Log:
Assessments - 3, GPA: 3.7 ( )

Instruções de Operação Superior, Modelo CDCR-CEN

Fabricante : Superior
Arquivo Tamanho: 4.28 mb
Arquivo Nome : Lennox_Hearth_CDST-PF-CL-CR_Installation_700001M.pdf
Língua de Ensino: en
Ir para baixar



Facilidade de uso


Ensure the ignitor lights the pilot. The pilot flame should engulf the flame rod as shown in Figure 56. 1. Visually inspect the gasket on the backside of the panels. The gasket surface must be clean, free of irregularities and seated firmly. 2. Position the glass enclosure panel in front of the firebox opening at a 45 degree angle and engage the top flange over the lip at the top of the firebox opening. See Figure 57. 3. Swing the glass enclosure panel down and back. Ensure the gasket seats evenly as the panel draws shut. Engage the Vee-flange at the bottom of the panel with the latches and close the latches to secure the panel. Step 11. HOOD INSTALLATION Step 11. HOOD INSTALLATION On all clean face units, slide the hoods into the slots on the lower edges of the radiant panels(Figure59). On louvered face units, slide the hoods into the slots on the lower edges of the cabinet top.(Figure 60). FINISHING REQUIREMENTS Wall Details Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (Figures 59 and 60) Combustible Finished Wall Materials This Area Must Remain Clear of Combustible Materials Top of Appliance 1" Min (25 mm) Combustible Wall FramingSpacer Top of Door Frame Radiant panel DrywallBracket/Spacer Combustible Wall Framing Hood must be installed as shown. Clean Face Models Figure 59 25NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 12 (305) MANTEL 10 (254) MANTEL 8 (203) MANTEL 6 (152) MANTEL 4 (102) MANTEL 4 (102) 14 (356) 12 (305) 10 (254) 2 (51) MANTEL TOP OF APPLIANCE 6 (152) NOTE - Hood shown as positioned in flush faced model. The hood position in the louvered front model is higher than shown. 8 (203) MANTEL CLEARANCES Inches (mm) Figure 62 COLD CLIMATE INSULATION If you live in a cold climate, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Combustible materials may project beyond the sides of the fireplace opening as long as they are kept within the shaded areas illustrated in Figure 61. Figure 61 A hearth extension is not required with this appliance. If a hearth extension is used, do not block the control compartment access panel. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements. 17" 14" Min. Distance To Unprotected Side Wall 8 ..." 45° Combustible Materials Allowed In Shaded Area “Safe Zone” 12" 5" Min. Distance To Protected Side Wall Top View OfFireplace Side Wall Side Wall Note:Combustible wall finish materials and/ or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face. See Figures 59 or 60. Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance front face with these exceptions: they must not cover any portion of the glass or louvers; they may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel up to the installed hood. Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 62. Mantels constructed of non-combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the hood. Framing Combustible Finished Wall Materials Combustible Wall Framing Spacer DrywallBracket/Spacer Top of Appliance Top of Door Frame Louvers This Area Must Remain Clear of Combustible Materials 1" Min (25 mm) Combustible Wall Hood must be installed as shown. Louver Face Models Figure 60 26 NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. *All compressed flex vents can be expanded up to two times. INSTALLATION ACCESSORIES Listed Secure Vent™Components Cat.No. Model No. Description H1968 SV4.5HT-2 Horizontal Square Termination with Firestop/Spacer (96K80) and Adapter (74L61) H2152 SV4.5CGV-1 Vertical Termination 77L70 SV4.5L6 6 inch (152 mm) Vent Section 77L71 SV4.5L12 12 inch (305 mm) Vent Section 77L72 SV4.5L24 24 inch (610 mm) Vent Section 77L73 SV4.5L36 36 inch (914 mm) Vent Section 77L74 SV4.5L48 48 inch (1219 mm) Vent Section 77L75 SV4.5LA Telescopic Section 77L76 SV4.5E45 45 Degree Elbow 77L77 SV4.5E90 90 Degree Elbow The following flashings come packaged with a storm collar. 77L78 SV4.5F Flat Roof Flashing 77L79 SV4.5FA 1/12 to 7/12 Adjust. Flashing 77L80 SV4.5FB 7/12 to 12/12 Adjust. Flashing 77L81 SV4.5SC6 Storm Collars (6 collars/box) 96K80 SV4.5HF Firestop/Spacer - Horizontal (3-1-1 spacing) 96K87 SV4.5VF Firestop/Spacer - Vertical (1-1-1 spacing) 96K93 SV4.5SU Support Strap 96K94 SV4.5RSA Attic Insulation Shield 96K92 SV4.5SP Support Plate 17M52 S...

Este manual também é adequado para os modelos :
Lareiras - CDCL-CEP (4.28 mb)
Lareiras - CDCL-CEN (4.28 mb)
Lareiras - CDCL-CMN (4.28 mb)
Lareiras - CDCL-CMP (4.28 mb)

Escreva a sua própria avaliação do dispositivo



Mensagem
Seu nome :
Introduza os dois dígitos :
capcha





categorias