|
Facilidade de uso
(In.) x Ht.(Ft.) (4X5) 24V EI WATER MBH STEAM MBH STEAM SQ. FT. WATER STEAM WATER STEAM IN3 62 51 44 38 158 81.0 80.0 83.1 81.9 350 4 x 15 IN4 105 87 76 65 271 81.3 80.0 83.1 82.0 420 5 x 15 IN5 140 115 100 86 358 81.6 80.3 83.1 82.0 485 6 x 15 IN6 175 144 125 108 450 81.8 80.6 83.2 82.1 555 6 x 15(5) IN7 210 173 150 130 542 82.1 80.9 83.2 82.1 620 7 x 15 IN8 245 202 176 152 633 81.1 80.0 83.2 82.2 690 7 x 15(5) IN9 280 231 201 174 725 81.4 80.3 83.2 82.2 760 8 x 15 AGA/CGA GROSS COMBUSTION EFFICIENCY (%) OUTPUT MBH WATER STEAM IN10(3) 315 259.87 226 195 812 83.5 82.5 815 8x15(5) IN11(3) 349 287.92 250 216 900 83.5 82.5 885 9x15 IN12 385 317.62 276 239 996 83.5 82.5 955 9x15 * LP available on IN3-IN9 1. Ratings shown are for installations at sea level and elevations up to 2,000 ft. For elevations above 2,000 ft., ratings should be reduced at the rate of four percent (4%) for each 1,000 ft. above sea level. 2. Capacities, outputs and ratings are based on steam combustion efficiency of 82.5%. Water combustion efficiency is 83.5%. 3. For Canadian builds only: Reduce input and output and by 3%. 4. 15 ft. height is measured from top of drafthood to top of chimney. 5. IN6, IN8, & IN10 - Canada only: Increase chimney diameter by 1". Working Pressure: 15 PSI Steam; 30 PSI Water...
Este manual também é adequado para os modelos :Aquecedores de Água - Independence IN10(3) (23.32 kb)
Aquecedores de Água - Independence IN12 (23.32 kb)
Aquecedores de Água - Independence IN3 (23.32 kb)
Aquecedores de Água - Independence IN4 (23.32 kb)